  • CURRENT SENSING RELAY
  • 0.1 - 1A
  • Adjustable 0.1-10 Second
  • 120V AC
  • 10A SPDT
Description Of Function The pick-up current setting is user-adjustable within the Monitored Current Range below. An external current transformer can be used to extend the range beyond 10 amperes. The drop-out setting is adjustable from 50-95% of the selected pick-up setting. The relay will energize when the monitored AC current is above the pick-up setting for a period longer than the adjustable time delay (t) of 0.1-10 seconds. This delay prevents nuisance tripping caused by inrush currents. It will de-energize when the monitored AC current is below the drop-out setting.
Function Chart
Application Information
  • Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.
  • Load (Burden): Less than 5VA for all voltages
  • Indicator LED: Green when Input Voltage is applied; Red when Relay is energized
  • Monitored Current Ranges: 0.1 - 1A
  • Response Times: Adjustable time delay of 0.1-10 seconds on pick-up; Fixed 100ms on drop-out
  • Output Contacts: 10A @ 240V AC / 7A @ 28V DC SPDT, 1/4 HP @ 120V AC (N.O.)
  • Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations
  • Temperature: -28o to 65o C (-18o to 149o F)
  • Approvals:

    c-ur-us.jpg  UL-socket.jpg
Dimensions - Inches (Millimeters)
Macromatic Distributor Stock Status
  • Allied Distributor Part #: 70175140 Info/Buy

Contact Macromatic

Fill out this form to have Macromatic contact you about this product.

©2024 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap
Knowledgebase General | Alternating Relays | Current Sensing Relays | Intrinsically Safe Barrier Relays | Liquid Level Control Relays | Seal Leak Relays | Three-Phase Monitor Relays | Time Delay Relays | Voltage Monitor Relays