LCP2E100

Use Socket: 70169-D

May not be exact product—for reference only.

  • LIQUID LEVEL CONTROL RELAY
  • DUAL PROBE PUMP UP
  • Sensitivity Range: 4.7K - 100K Ohms
  • 120V AC
  • 10A SPDT
Description Of Function

Pump Up (Fill): When the liquid level falls below the low level probe, a 1 second time delay begins & the LED flashes Red. At the end of the time delay, the output relay energizes & the LED is Red ON. The pump is ON to fill the tank. The relay remains energized until the liquid level rises & touches the high level probe. The output relay de-energizes, turning off the pump, and remains de-energized & the LED is Green ON until the liquid level again falls below the low level probe.

Function Chart
Application Information
  • Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.
  • Load (Burden): 2 VA
  • Indicator LEDs: Green ON with Input Voltage applied; Red Flashing during timing; Red ON when relay energized.
  • Probe Voltage: 5V DC Pulsed
  • Response Time: Pick-up: 1 second; Drop-out: 1 second
  • Output Contacts: 10A @ 240V AC/7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
  • Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations
  • Temperature: -28o to 65o C (-18o to 149o F)
  • Approvals:

    c-ur-us.jpg  CULUS-with-socket.jpg  
Dimensions - Inches (Millimeters)
Macromatic Distributor Stock Status
  • Allied Distributor Part #: 70988117 Info/Buy

  • Galco Distributor Part #: LCP2E100 Info/Buy

Contact Macromatic

Fill out this form to have Macromatic contact you about this product.

©2024 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap
Knowledgebase General | Alternating Relays | Current Sensing Relays | Intrinsically Safe Barrier Relays | Liquid Level Control Relays | Seal Leak Relays | Three-Phase Monitor Relays | Time Delay Relays | Voltage Monitor Relays