Description Of Function

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized. Any one of three fault conditions will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting (see right).

Application Information
  • Load (Burden): Less than 40 VA
  • Response Times:
    Power Up/Restart After Fault: Fixed at 1 Seconds
    Drop-out Due to:
      Phase Loss & Reversal:
      Undervoltage:

    100ms Fixed
    Fixed 4 Seconds
  • Minimum/Maximum Voltage: 156-198V (PAP208); 180-230V (PAP240); 330-380V (PAP400); 360-460V (PAP480); 431-546V (PAP575), all 50/60Hz. +5%
  • Reset: Automatic upon correction of fault.
  • Output Contacts: 10A @ 277V AC / 7A @ 30V DC;
    1HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty
  • Life: Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Temperature: -28o to 65o C (-18o to 149o F)
  • Approvals:

    c-ur-us.jpg  CE_Logo.gif  UL-socket.jpg
Dimensions - Inches (Millimeters)
Macromatic Distributor Stock Status
  • Allied Distributor Part #: 70175173 Info/Buy

  • Grainger Distributor Part #: 5WMJ4 Info/Buy

Contact Macromatic

Fill out this form to have Macromatic contact you about this product.

©2024 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap
Knowledgebase General | Alternating Relays | Current Sensing Relays | Intrinsically Safe Barrier Relays | Liquid Level Control Relays | Seal Leak Relays | Three-Phase Monitor Relays | Time Delay Relays | Voltage Monitor Relays