PCP575

Use Socket: 70169-D

May not be exact product—for reference only.

  • 3-PHASE MONITOR RELAY
  • PHASE REVERSAL
  • 460-600V AC
  • 10A SPDT
Description Of Function

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized. An out-of-sequence condition will prevent the relay from energizing on start-up or trip the relay if it occurs when it is energized. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates both a normal condition with the proper phase sequence (solid GREEN) or a fault condition with the phases out of sequence (solid RED).

Application Information
  • Load (Burden): Less than 40 VA
  • Response Times:
    Power Up/Restart After Fault: Fixed at 1 Seconds
    Drop-out Due to:
      Reversal:

    100ms Fixed
  • Minimum/Maximum Voltage: 156-550V (PCPU); 345-660V (PCP575), all 50/60Hz. +5%
  • Reset: Automatic upon correction of fault.
  • Output Contacts: 10A @ 277V AC / 7A @ 30V DC;
    1HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty
  • Life: Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Temperature: -28o to 65o C (-18o to 149o F)
  • Approvals:

    c-ur-us.jpg  CE_Logo.gif  UL-socket.jpg
Dimensions - Inches (Millimeters)
Macromatic Distributor Stock Status
  • The PCP575 is not stocked by any Macromatic distributor. Please see below for any product substitutions.

    Contact Macromatic for more information or how to purchase this product.

Contact Macromatic

Fill out this form to have Macromatic contact you about this product.

©2024 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap