PLP575

Use Socket: 70169-D

May not be exact product—for reference only.

  • 3-PHASE MONITOR RELAY
  • PHASE LOSS & PHASE REVERSAL
  • 460-600V AC
  • 10A SPDT
Description Of Function

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized. A phase loss or phase reversal condition will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting (see right).

Application Information
  • Load (Burden): Less than 40 VA
  • Response Times:
    Power Up & Restart After Fault: Fixed 1 Second
    Drop-out Due to Fault:
      Phase Loss & Reversal

    100ms Fixed
  • Minimum/Maximum Voltage: 156-550V (PLPU); 345-660V (PLP575), all 50/60Hz. +5%
  • Reset: Automatic upon correction of fault.
  • Output Contacts: 10A @ 277V AC / 7A @ 30V DC;
    1HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty
  • Life: Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Temperature: -28o to 65o C (-18o to 149o F)
  • Approvals:

    c-ur-us.jpg  CE_Logo.gif  UL-socket.jpg
Dimensions - Inches (Millimeters)
Macromatic Distributor Stock Status
  • The PLP575 is not stocked by any Macromatic distributor. Please see below for any product substitutions.

    Contact Macromatic for more information or how to purchase this product.

Contact Macromatic

Fill out this form to have Macromatic contact you about this product.

©2024 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap
Knowledgebase General | Alternating Relays | Current Sensing Relays | Intrinsically Safe Barrier Relays | Liquid Level Control Relays | Seal Leak Relays | Three-Phase Monitor Relays | Time Delay Relays | Voltage Monitor Relays