RT26A-10

May not be exact product—for reference only.

  • RESET TIMER
  • RESET
  • 1.8-180 SEC
  • 120V AC
  • 10A SPDT
Description Of Function Upon application of input voltage, the time delay (t) begins. If a reset signal is applied during time delay (t), the time delay (t) is reset. At the end of time delay (t), the output relay is energized and the N.C. contact opens. If a reset signal is applied after time delay (t) has elapsed, time delay (t) is reset and relay output is de-energized. Upon removal of the reset signal either during time delay (t) or after the time delay (t) has elapsed, the time delay (t) is reset to zero. The timer uses the NC contact which opens on timeout. The time delay (t) and relay status are retained using non-volatile memory in the event of a power loss using the RESET function. The RESET (NO MEMORY) function operates in the same manner except that time delay (t) and relay status are not retained in the event of a power loss.
Application Information
  • Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz
  • Load (Burden): 2 VA
  • Setting Accuracy: Maximum Setting: +5%, -0%; Minimum Setting: +0%, -50%;
  • Repeat Accuracy (Constant Voltage & Temperature): +0.1% or + 0.04 seconds, whichever is greater
  • Indicator LEDs:
    Red (ON) during timing
    Red Flashing when reset signal applied
    OFF when timed out or input voltage removed
  • Output Contacts: 10A @ 240VAC / 7A @ 28VDC SPNO, 1/4hp @ 120VAC (N.O.)
  • Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations
  • Temperature: -28o to 65o C (-18o to 149o F)
  • Approvals:

    c-ur-us.jpg  CE_Logo.gif  
Dimensions - Inches (Millimeters)
Macromatic Distributor Stock Status
  • The RT26A-10 is not stocked by any Macromatic distributor. Please see below for any product substitutions.

    Contact Macromatic for more information or how to purchase this product.

Contact Macromatic

Fill out this form to have Macromatic contact you about this product.

©2024 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap
Knowledgebase General | Alternating Relays | Current Sensing Relays | Intrinsically Safe Barrier Relays | Liquid Level Control Relays | Seal Leak Relays | Three-Phase Monitor Relays | Time Delay Relays | Voltage Monitor Relays