  • TIME DELAY RELAY
  • ON/OFF DELAY
  • 0.1 - 10 hr
  • 24V AC/DC
  • 10A SPDT
Description Of Function Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the time delay (t1) begins. At the end of the time delay (t1), the output is energized. When the trigger is removed, the output contacts remain energized for the time delay (t2). At the end of the time delay (t2), the output is de-energized & the time delay relay is ready to accept another trigger. If the trigger is removed during time delay period (t1), the output will remain de-energized and time delay (t1) will reset. If the trigger is reapplied during time delay period (t2), the output will remain energized and the time delay (t2) will reset.
Function Chart
Application Information
  • Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz; DC Operation: +10/-15% of nominal.
  • Load (Burden): Maximum of 2 VA for all voltages
  • Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%; Minimum Setting (Adjustable): +0%, -50%; Fixed Time Delay: +2% or 50ms, whichever is greater
  • Repeat Accuracy (Constant Voltage & Temperature): +0.1% or + 0.04 seconds, whichever is greater
  • Reset Time: 100ms
  • Output Contacts: 10A @ 240VAC / 7A @ 28VDC, 1/4hp @ 120VAC (N.O.)
  • Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations
  • Temperature: -28o to 65oC (-18o to 149oF)
  • Approvals:

    c-ur-us.jpg  CE_Logo.gif  
Dimensions - Inches (Millimeters)
Macromatic Distributor Stock Status
  • The THR-14168-34JT is not stocked by any Macromatic distributor. Please see below for any product substitutions.

    Contact Macromatic for more information or how to purchase this product.

Contact Macromatic

Fill out this form to have Macromatic contact you about this product.

©2024 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap
Knowledgebase General | Alternating Relays | Current Sensing Relays | Intrinsically Safe Barrier Relays | Liquid Level Control Relays | Seal Leak Relays | Three-Phase Monitor Relays | Time Delay Relays | Voltage Monitor Relays