Competitive Cross Reference
Macromatic offers this cross-reference as a service to our customers to assist in the selection of replacement products. Every effort has been made to insure that these products are electrically and functionally equivalent to the Macromatic products except as noted. Macromatic cannot be responsible for errors of printing or corrections of data taken from published competitive data. It is the user's responsibility to insure the suitability of the substitution.
If you have any questions regarding these cross-references, or need to cross reference any product not listed, please contact Macromatic.
* If a part number is not found, select the "Series Name" from the right-hand drop down.
Or select competitor part series:

800.238.7474
Product Specifications
TCF8F


Use socket: IDEC SR6P-M11G (Included)
Image may not be exact product—for reference only.
Competitor: Flygt (Xylem)
- Competitor Part #: 14-407129
- Series: 14
- Macromatic Equivalent: TCF8F
- Differences: The Flygt unit will work on either 120V AC or 24V AC/DC using terminals 2, 6 & 10; the Macromatic product is 24V AC only on pins 2 & 10; the Macromatic unit is approximately one-half inch shorter than the Flygt unit; the Macromatic unit has two dual-color LEDs to indicate both Normal & Fault while the Flygt unit has two red-only LEDs to indicate Fault only & one green-only LED to indicate Power
- Family: SEAL LEAKAGE & OVER TEMPERATURE RELAY
- Function: OVER TEMPERATURE & SEAL LEAKAGE | AUTO & MANUAL RESET | FOR USE W/ FLS & CLS SENSORS
- Input Voltage: 24V AC
- Output: (2)7A SPDT
Description of function:
With input voltage applied, normal temperature condition (thermal switch closed) and no seal leakage, the sensor current will be in the normal range. The over temperature relay is energized and the seal leak relay is de-energized. Both LEDs are Green, indicating normal conditions and input voltage applied.
When the motor temperature rises and the N.C. thermal switch opens, the sensor current drops to zero. The over temperature relay is de-energized, opening a contact that had been closed and turning off the pump contactor. The TEMP LED turns Red. If the over temperature condition is cleared, the unit will reset based on the setting of the Over Temp switch. In the AUTO mode, the unit will reset automatically. In the MANUAL mode, the Over Temp Reset button must be pushed to clear the alarm and reset the relay.
In a seal leakage condition, contaminating fluid enters the pump motor cavity. The sensor lowers its resistance, increasing the sensor circuit current above the trip point. The seal leakage output relay energizes and closes a contact, which can be used to give an alarm indication of a leaking seal. The LEAK LED turns Red.
If either an Over Temp fault condition when the Over Temp switch is set to AUTO or a Seal Leakage fault has been automatically cleared, a cleared fault indication is displayed by flashing the corresponding Red TEMP LED or Red SEAL LED. The flashing indication may be manually reset by pressing the Over Temp Reset button. Note: if either fault still exists when the Over Temp Reset button is depressed, it is ignored.
If the sensor wires are shorted, the unit will display a Shorted Sensor condition by alternately flashing the Red SEAL LED and the Red TEMP LED. If the short is removed, the fault will automatically reset within 30 seconds.
Application Information
- Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.
- Load (Burden): 3 VA
- Indicator LEDs:
Seal Leak: Green ON with input voltage applied; no seal leak and relay energized; Red ON when seal leak detected and relay de-energized
Temperature: Green ON with input voltage applied, normal temperature condition and relay energized; Red ON when over temperature detected and relay de-energized - Probe Voltage: 5V DC
- Response Time: Pick-up & Drop-out: 1 Second
- Output Contacts: 7A @ 240V AC/7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
- Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations
- Temperature: -28o to 65o C (-18o to 149o F)
- Approvals:
Dimensions
Inches (Millimeters)