Competitive Cross Reference
Macromatic offers this cross-reference as a service to our customers to assist in the selection of replacement products. Every effort has been made to insure that these products are electrically and functionally equivalent to the Macromatic products except as noted. Macromatic cannot be responsible for errors of printing or corrections of data taken from published competitive data. It is the user's responsibility to insure the suitability of the substitution.
If you have any questions regarding these cross-references, or need to cross reference any product not listed, please contact Macromatic.
* If a part number is not found, select the "Series Name" from the right-hand drop down.
Or select competitor part series:

800.238.7474
Product Specifications
VMP240AX


Use socket: 70169-D
Image may not be exact product—for reference only.
Competitor: Symcom
- Competitor Part #: 201-200-SP-DPDT
- Series: 201-200
- Macromatic Equivalent: VMP240AX
- Differences: The Macromatic unit is rated 5A while the Symcom unit is rated 10A.
- Family: VOLTAGE MONITOR RELAY
- Function: OVER/UNDER VOLTAGE
- Timing: Fixed Time Delay on Pick-up & Drop-out 0.5 Seconds
- Monitored Voltage: 240VAC
- Output: 5A DPDT
Description of function:
Function Chart:
Application Information
- Voltage Tolerance: +50%/-50% of nominal AC voltage (50-60Hz, +5%); No separate input voltage is required since unit is powered by monitored voltage.
- Load (Burden): 30VA
- Voltage Settings:
Pick-up (Umax): Adjustable across full range as shown on the product nameplate
Drop-out (Umin): Fixed at 95% of the Pick-up setting - Response Times: Pick-up: 500 ms; Drop-out (t): Fixed 0.5 Seconds
- Indicator LED: Red when Relay is energized; Green when Relay is Off
- Output Contacts: 5A @ 277V AC / 30V DC;
1/3HP @ 120/240V AC; B300 Pilot Duty - Life: Mechanical: 10,000,000 operations, Full Load: 100,000 operations
- Temperature: -28o to 65o C (-18o to 149o F)
- Approvals:


Dimensions
Inches (Millimeters)