Macromatic offers this cross-reference as a service to our customers to assist in the selection of replacement products.  Every effort has been made to insure that these products are electrically and functionally equivalent to the Macromatic products except as noted.   Macromatic cannot be responsible for errors of printing or corrections of data taken from published competitive data.  It is the user's responsibility to insure the suitability of the substitution.

If you have any questions regarding these cross-references, or need to cross reference any product not listed, please contact Macromatic.

* If a part number is not found, select the "Series Name" from the right-hand drop down.

Macromatic Equivalent

Catalog Number: LCP2D250

Use Socket: 70169-D

May not be exact product—for reference only.

  • LIQUID LEVEL CONTROL RELAY
  • DUAL PROBE PUMP DOWN
  • Sensitivity Range: 1K - 250K Ohms
  • 120V AC
  • 10A SPDT
Ingram Product
  • Competitor Part # LLC2P120A | Series: Liquid Level Control

    Differences:

    Ingram LLC2P120A is selectable between pump up or pump down applications with 120V AC control. For pump up applications, use the Macromatic LCP2C250. For pump down applications, use Macromatic LCP2D250. Ingram has a sensitivity range of 500 to 100K Ohms and the Macromatic LCP2D250 has a range of 1K – 250K Ohms. Ingram has a 4 amp SPDT output while Macromatic has a 10 amp SPDT output. Ingram has an adjustable response time of 0.5 – 10 sec while Macromatic has a 1 sec fixed pick-up and 1 sec fixed drop-out. Ingram LED single color and activates when relay energized while Macromatic LED is multi-colored: Green ON with input voltage applied, Red flashing during timing; Red ON when relay energized. Ingram has 100,000 Mechanical / 50,000 Electrical Life expectancy while Macromatic has 10,000,000 Mechanical / 100,000 Electrical. Both are 120V rated with 8 socket configuration and similar dimensions.

Description Of Function

Pump Down (Drain): When the liquid level rises & touches the high level probe, a 1 second time delay begins & the LED flashes Red. At the end of the delay, the output relay energizes & the LED is Red ON. The pump is ON to drain the tank. The relay remains energized until the liquid level falls below the low level probe. The output relay de-energizes, turning off the pump, and remains de-energized & the LED is Green ON until the liquid level rises & touches the high level probe.

Function Chart
Application Information
  • Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.
  • Load (Burden): 2 VA
  • Indicator LEDs: Green ON with Input Voltage applied; Red Flashing during timing; Red ON when relay energized.
  • Probe Voltage: 5V DC Pulsed
  • Response Time: Pick-up: 1 second; Drop-out: 1 second
  • Output Contacts: 10A @ 240V AC/7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
  • Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations
  • Temperature: -28o to 65o C (-18o to 149o F)
  • Approvals:

    c-ur-us.jpg  CULUS-with-socket.jpg  
Dimensions - Inches (Millimeters)
Macromatic Distributor Stock Status
  • The LCP2D250 is not stocked by any Macromatic distributor. Please see below for any product substitutions.

    Contact Macromatic for more information or how to purchase this product.

Contact Macromatic

Fill out this form to have Macromatic contact you about this product.

 

 

©2026 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap
Knowledgebase General | Alternating Relays | Current Sensing Relays | Intrinsically Safe Barrier Relays | Liquid Level Control Relays | Seal Leak Relays | Three-Phase Monitor Relays | Time Delay Relays | Voltage Monitor Relays