Control Switch Jumpered on TD-7 Digital-Set Time Delay Relay

Thursday: October 22, 2015 : Time Delay Relays


Issue:

What happens if I put a jumper across the control switch terminals (Pins 5 & 6) on the TD-7 Digital-Set time delay relay, but I have the function set to On Delay, which doesn't need a Control Switch to initiate it? Will the unit operate satisfactorily?

Solution/Resolution:

No control switch is required when the unit is set to On Delay, Interval On, Flasher (OFF 1st) or Flasher (ON 1st). However, if for any reason Pins 5 & 6 have been jumpered before Input Voltage is applied when set to one of these functions, the unit will operate without any problems. The software program is written to ignore Pins 5 & 6 when either of these four functions are selected using the first pushbutton-thumbwheel.

Of course, when in the Off Delay, Single Shot, Watchdog, Triggered On Delay, On/Off Delay or Single Shot (Falling Edge) mode, a dry contact control switch must be connected to Pins 5 & 6 to initiate the function. If the trigger across Pins 5 & 6 is closed when Input Voltage is applied, the unit will recognize the closed trigger and operate normally. For more information on the operation of any triggered Macromatic time delay relay with the trigger closed & Input Voltage applied, click here.

Click here for additional information on understanding time delay functions.

©2024 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap
Knowledgebase General | Alternating Relays | Current Sensing Relays | Intrinsically Safe Barrier Relays | Liquid Level Control Relays | Seal Leak Relays | Three-Phase Monitor Relays | Time Delay Relays | Voltage Monitor Relays