TD-881 Series DIP Switch Programming

Tuesday: July 30, 2019 : Time Delay Relays



 
 
 
Single
Mode (t)
Dual Mode
FUNCTION
TIME BASE
ON OFF ON
COMBINE FOR
TOTAL TIME
 
A
1
1
B
2
2
C
4
t1  4
D
8
     8
E
16
16
F
32
1
G
64
2
H
128
t2  4
J
256
8
K
512
16
 

 

Tips for Printing Page

To ensure the graphic is printed correctly, use the following directions for each browser:

  • Internet Explorer—Page Setup (Alt+U) / Check “Print Background Colors and Images”
  • Chrome—Print Preview / More Settings / Check “Background graphics”
  • Firefox—Page Setup / Check “Print Background (colors & images)”

Tips for Setting Time Delay

Depending on the function selected, not every time delay is possible with this unit.  For example, time delays of 12.55 Seconds or 145.5 Minutes are not valid settings for Single Mode functions.  The Dual Mode functions are even more limited due to the fact that five switches are used for time t1 and 5 switches are used for time t2. 

Use the following tables to determine what time delays are valid.  If you cannot set the exact delay you want, then find one as close as possible.  For example, if you want a delay of 12.55 Seconds for a Single Mode function, which is not valid, select 12.5 Seconds or 12.6 Seconds.  If you need a t1 or t2 delay of 40 Seconds for a Dual Mode function, which is not valid, the best option is to select 0.7 Minutes or 42 Seconds.

Single Mode (Time) Functions
Includes On Delay, Interval On, Off Delay, Triggered On Delay, Flasher (ON 1st), Flasher (OFF 1st), Watchdog, One Shot Falling Edge and Single Shot
Time Base MIN Time Max Time
0.01S 0.01S 10.23S
0.1S 0.1S 102.3S
1S 1S 1,023S
0.1M 0.1M 102.3M
1M 1M 1,023M
0.1H 0.1H 102.3H
1H 1H 1,023H
10H 10H 10,230H
Dual Mode (Time) Functions
Includes Cycle (ON 1st), Cycle (OFF 1st), Delayed Interval, On/Off Delay, Triggered Delayed Interval, One Shot-Flasher and On Delay/ Flasher
Time Base MIN Time Max Time
0.01S 0.01S 0.31S
0.1S 0.1S 3.1S
1S 1S 31S
0.1M 0.1M 3.1M
1M 1M 31M
0.1H 0.1H 3.1H
1H 1H 31H
10H 10H 310H

©2024 Macromatic Industrial Controls, Inc.