Protection on a Corner Grounded Delta System
Issue:
Can I use a phase monitor for protection on a corner grounded delta system?
Answer:
Yes, Macromatic phase monitor relays provide the same reliable protection on corner grounded delta systems.
A corner grounded delta system is a common way to establish a reference to safety ground when dealing with an otherwise floating output from a delta secondary transformer. It is implemented by grounding any one of the three phases of the transformer secondary (corners of the delta).
In order to apply a phase monitor relay in this type of installation, it is important to realize that despite the connection to ground the three phase delta output remains unchanged. A phase monitor relay should be connected to phases A, B, & C (one of which will be grounded) as you would in any standard application.
Please contact Macromatic for more details.