Understanding Entity Parameters

Monday: July 15, 2019 : Intrinsically Safe Barrier Relays


Designing Intrinsically Safe Circuits

When designing Intrinsically Safe Circuits, it is imperative to understand the entity parameters of the devices in your circuit. The entity parameters describe characteristics of the device, as well as what can safely be connected to it. As discussed in Intrinsic Safety Overview, the three components of an Intrinsically Safe Circuit are the field device, field wiring, and the barrier.

Field devices can be broken into two types, simple and non-simple devices. Simple devices are defined as devices that do not generate or store more than 1.2V potential, 100mA current, 20uJ energy, and 25mW power. Simple devices do not have entity parameters.

Non-simple devices must be certified as intrinsically safe for use in hazardous areas; a certified non-simple device is referred to as an Intrinsically Safe Apparatus. These devices will be marked with, or have accompanying documentation, providing entity parameters that govern their safe use as a field device within an intrinsically safe circuit.

Entity Parameters can be broken into two different categories, Associated Apparatus (devices that are installed in the safe area and interface between Hazardous Location and the safe location) and Intrinsically Safe Apparatus (non-simple devices that are installed in the Hazardous Location).

 

Entity Parameters for Associated Apparatus

Uo/Voc Maximum voltage passed into Hazardous Location
Io/Isc Maximum current passed into Hazardous Location
Po Maximum power passed into Hazardous Location
Co/Ca Maximum capacitance that can be connect to device
Lo/La  Maximum inductance that can be connected to device

 

Entity Parameters for Intrinsically Safe Apparatus

Ui/Vmax Maximum voltage that can be connected to device
Ii/Imax Maximum current that can be connected to device
Pi Maximum power that can be connected to device
Ci Maximum internal capacitance of the device
 Li Maximum internal inductance of the device

 

When designing an Intrinsically Safe circuit (field device, field wiring, and barrier) each of the following must be true.

Vmax ≥ Voc

Imax ≥ Isc

Ci + Ccable ≤ Ca

 Li + Lcable ≤ La

Most of these values above can be gathered from documentation provided with the barrier and field device used. The capacitance (Ccable) and inductance (Lcable) of cable must be calculated using the two following equations. The inductance and capacitance values per foot used below are the default “worst case” parameters established for use when actual properties of the wire/cable are not known. Actual wire/cable properties can be substituted in place of these when available.

Lcable = 0.2uH/foot * feet of cable

Ccable = 60pF/foot * feet of cable

Macromatic ISEUR1 Intrinsically Safe Barrier Relay

Design Example

In this example, the Macromatic ISEUR1 Intrinsically Safe Barrier Relay is the “barrier” used to interface with the hazardous area. The associated apparatus entity parameters for the ISEUR1 are listed below.

Voc = 10.29V

Isc = 18.05mA

Ca= 2.63uF

La= 109.1mH

The ISEUR1 will be connected to a “field device” in the hazardous area. In this example, the field device is an Intrinsically Safe Apparatus and must meet the following requirements, based on the barrier entity parameters of the barrier, to maintain intrinsic safety.

Vmax ≥ 10.29V

Imax ≥ 18.05mA

Ci + Ccable ≤ 2.63uF

Li + Lcable ≤ 109.1mH

Assuming the Intrinsically Safe Apparatus that has the following Entity parameters:

Vmax = 15V

Imax = 30mA

Ci = 2uF

Li = 2mH

  • Vmax of 15V is greater than 10.29V required, this meets the requirement.
  • Imax of 30mA is greater than 18.05mA, this meets the requirement.

In order to verify the capacitance and inductance parameters, the capacitance and inductance of the interconnecting wire/cable must be calculated. For this example, we will assume a 500 foot long wiring run for 1000 total feet of cable.

Lcable = 0.2uH/foot * 1000 = 0.20mH

Ccable = 60pF/foot * 1000 = 0.060 uF

  • Ci + Ccable = 2.06uF, this is less than the 2.63uF limit and meets the requirement.
  • Li + Lcable = 2.2mH, this is less than the 109.1mH limit and meets the requirement.

The barrier, field device, and field wiring as described would be allowable based on entity parameters.

 

Calculating Maximum Wire/Cable Length

Sometimes the barrier and field device are known, but wire/cable length is not. In this situation, it can be more helpful to know the maximum length of wire/cable that would be allowable.

The allowable cable length can be calculated as follows:

Cable Length ≤ (Co-Ci)/(0.2uF/Foot) = (109.1mH-2mH)/(0.2uH/Foot) = 535,500 Ft

Cable Length ≤ (Lo-Li)/(60pF/Foot) = (2.63uF-2uF)/(60pF/Foot ) = 10,050 Ft

The maximum length of cable allowable is 10,050 feet, the lesser of the two values.
(Note: this is total length, the sum of the length of both supply and return conductors.)

 

The Macromatic ISD & ISE Series of Intrinsically Safe Barrier Relays provide a safe, reliable and cost-effective method to control loads (motor starters, relays, etc.) with input devices (switches, sensors, etc.) located in a hazardous area.

Learn More: An Overview of Hazardous Location Classification

 

©2024 Macromatic Industrial Controls, Inc.

2201 Corporate Drive
Waukesha, WI 53189

800-238-7474 • 262-781-3366

Rep Login | Newsletter Sign Up | Articles | Employment | Privacy Policy | Sitemap
Knowledgebase General | Alternating Relays | Current Sensing Relays | Intrinsically Safe Barrier Relays | Liquid Level Control Relays | Seal Leak Relays | Three-Phase Monitor Relays | Time Delay Relays | Voltage Monitor Relays