ISD Series

4-Channel | 60mm

ISDUR4 enables the selection of four operating configurations that apply to all channels

ISDUR4 enables the selection of four operating configurations that apply to all channels

ISDUM4 enables the selection of four operating configurations applied independently to each channel

ISDUM4 enables the selection of four operating configurations applied independently to each channel

Features
  • Approved for use in these hazardous environments:
    • Class I, Div 1 (Zones 0 and 1 Canada), Groups A,B,C,D
    • Class II, Div 1 (Zones 20 and 21 Canada), Groups E,F,G
    • Class III, Div 1
  • 4-Channel
  • Isolated input terminals
  • Isolated 5A relay outputs 
  • Pluggable terminals offer easy installation & replacement
  • Universal input voltage of 102-132V AC & 10-125V DC
  • Standard & inverse logic
  • Instantaneous & delayed response times  
  • LED status indicator
Enclosure Style Compact 60mm wide enclosure for both DIN-rail & panel mounting
Configuration/
Contact Rating
  • SPST-NO (Form A) 
  • 3A Resistive @ 125V AC @ 60oC & 30V DC Resistive, Pilot Duty Rating D300
  • 5A Resistive @ 125V AC @ 40oC & 30V DC Resistive, Pilot Duty Rating D300
Approvals        UL913 8th Edition    
Technical Documentation

Each ISD Series product consists of 4 intrinsically safe inputs and 4 corresponding electromechanical relay outputs.  With input voltage applied, the V LED will be ON (GREEN) to indicate power is applied.  When the input device is closed, the input LED is ON (GREEN).  When the output relay is energized, the output LED is ON (ORANGE). 

These products offer four operating configurations which are user selectable and easily accessible.

ISDUR4 has a two-position DIP-switch that enables the selection of configurations that apply to all channels. 

ISDUM4 has an eight-position DIP-switch with configurations applied independently to each channel.

Configurations applied: 

Standard Logic (DIP Switch set to “STD”):
When the input device in the hazardous area is closed, the corresponding output relay is energized.  When the input device opens, the corresponding output relay will de-energize.

Inverse Logic (DIP Switch set to “INV”):
When the input device in the hazardous area is open, the corresponding output relay is energized.  When the input device closes, the corresponding output relay will de-energize.

No Time Delay (DIP Switch set to “0 S”):
The output relay will have an immediate change in status in response to the input device closing or opening.

Fixed 2 Second Delay (DIP Switch set to “2 S”):
The output relay will delay 2 seconds before a change of status in response to the input device closing or opening.

ISDUR4 enables the selection of four operating configurations that apply to all channels

ISDUR4 enables the selection of four operating configurations that apply to all channels

ISDUM4 enables the selection of four operating configurations applied independently to each channel

ISDUM4 enables the selection of four operating configurations applied independently to each channel