PC Series
DIN-Rail Mounting with Communication
Equipment protection with industry leading communication technology via Modbus TCP
Features |
|
Enclosure Style | Mounts on 35mm DIN-rail or screw mounting with extendable clips |
Configuration/ Contact Rating |
|
Approvals | File #E109466 |
Technical Documentation |
Protection:
Phase Loss: Unit trips on loss of any Phase L1, L2 or L3, regardless of any regenerative voltages.
Phase Reversal (Out-of-Sequence): Unit trips if sequence (rotation) of the three phases is anything other than L1-L2-L3. It will not work on L3-L2-L1.
Phase Unbalance: Adjustable from 2 - 10% unbalance. Unit trips when any one of the three lines deviates from the average of all three lines by more than the adjusted set point for a period longer than the adjustable trip delay. It will reset at 80% of the unbalance trip setting.
Undervoltage: Adjustable from 80-95% of the line voltage setting. Unit trips when the average of all three lines is less than the adjusted set point for a period longer than the adjustable trip delay. It will reset at +2% of the undervoltage trip setting.
Overvoltage: Adjustable from 105-120% of the line voltage setting. Unit trips when the average of all three lines is greater than the adjusted set point for a period longer than the adjustable trip delay. It will reset at +2% of the overvoltage trip setting.
Modbus TCP:
Connector: RJ45
Connection speed: 10/100 Mb Full and Half Duplex
IP Addressing: Static (default), Dynamic (DHCP)
Macromatic's Three-Phase Monitor Relays Knowledge Base contains general and technical industry articles to help you learn more about Three-Phase Monitor Relays.
Equipment protection with industry leading communication technology via Modbus TCP